Model Number |
VCBI-12/630-20 |
■General
VCBI series high-voltage vacuum circuit breaker is a kind of indoor high-voltage switch equipment with 50Hz three-phase alternating current and 12Kv rated voltage, which combined the technique of the ABB Corporation in Switzerland and domestic development state and manufacturing capability. The general framework of this product is taken the form combined the front body and operation system into one.
Because it adopted the composite insulated material, there is no pollution and explosion danger, the insulation level is high.
■Technical parameter
|
Serial number
|
Item
|
Unit
|
Data
|
|
31.5kA
|
40kA
|
50kA
|
|
1
|
Rated voltage
|
kV
|
12
|
|
2
|
Maximum working voltage
|
kV
|
12
|
|
3
|
Rated current
|
A
|
1250,1600
2000,2500
|
1250,1600
2500,3150
|
1250,2500
3150
|
|
4
|
Rated short-circuit break current
|
kA
|
31.5
|
40
|
50
|
|
5
|
Rated short-circuit close current (peak value)
|
kA
|
80
|
100
|
125
|
|
6
|
Rated peak value withstand current
|
kA
|
80
|
100
|
125
|
|
7
|
4S Rated little withstand current
|
kA
|
31.5
|
40
|
50
|
|
8
|
Rated in sudation level
|
Industrial frequency withstand voltage
|
kV
|
45(fracture 84)
|
|
Thunder impulse withstand voltage
|
75(fracture 84)
|
|
9
|
Rated operation order
|
|
Off-0.3S on and off-180S-on and off
|
|
10
|
Mechanical life-span
|
Times
|
10000
|
|
11
|
Rated short-circuit current break and close time
|
Times
|
50
|
|
12
|
Speak and move organization amount equal to the voltage of the floodgate (DC)
|
V
|
110,220
|
|
13
|
Speak and move organization amount assign the current of the floodgate (DC)
|
V
|
110,220
|
|
14
|
Switching distance of the contact
|
mm
|
11±1
|
|
15
|
Ultra journey (touches the head spring and compress length)
|
mm
|
4±0.5
|
|
16
|
Three-phase breaking into 、shut floodgate sex of the same period
|
ms
|
≤2
|
|
17
|
Touch the head and shut a floodgate of time of bouncing
|
ms
|
≤2
|
|
18
|
Average speed of breaking brake
|
M/s
|
0.9~1.2
|
|
19
|
Average speed of closing brake
|
M/s
|
0.6~0.8
|
|
20
|
Time of breaking brake
|
Operate it under the voltage highest
|
S
|
≤0.05
|
|
Operate it under the voltage the most low
|
≤0.08
|
|
21
|
Time of closing brake
|
S
|
≤0.1
|
|
22
|
Each the resistance of main return circuit
|
μΩ
|
≤40
|
|
23
|
Allowance abrasion cumulated thickness of the moving and stationary contact
|
mm
|
3
|
|